Wolverine Power Supply Cooperative - Permitting Information
1. Facility Information
Wolverine Power Supply Cooperative
2. Location
Rogers City, Presque Isle County, MI
3. Distance from US/Canada Border
about 50 km
4. Facility Type and Size
Installation of 600 MW solid fuel-fired power plant at existing Oglebay Norton quarry property
5. Sources of Emissions
Boilers
6. Type of Fuel
Primary Fuel:
• Mainly Powder River Basin coal (low sulfur) with a blend of up to 70% by Btu of petroleum coke (pet coke). Also coal from Canada and other US regions, if desired.
Secondary fuel:
• 100% Illinois Basin coal (high sulfur content). On the basis of annual energy consumption, up to 20% by Btu biomass will be burned as supplementary fuel.
7. Type and Quantity of Emissions
NOx:
• 0.07 lb/MMBtu (30-day avge) during normal operation - excluding periods at SSM - at loads greater than or equal to 70% load
• 0.14 lb/MMBtu ( 30-day rolling avge) during low load operation, loads less than 70% load but greater than 50%
SO2:
• 0.06 lb/MMBtu (30-day avge) during normal operation, excluding periods at SSM at loads greater than or equal to 70% load
• 0.05 lb/MMBtu as an annual avge during normal operation;
• 0.08 lb/MMBtu (30-day avge) during low load operation, excluding periods at SSM at loads less than 70% load but greater than 50% load
• 0.10 lb/MMBtu (3-hr rolling avge) during normal operation low load operation, excluding periods at SSM at loads less than 70% load but greater than 50%
Filterable PM10: 0.010 lb/MMBtu
CO: 0.15 lb/MMBtu (30-day avg)
VOC: 0.0035 lb/MMBtu
H2SO4: 0.006 lb/MMBtu
8. Emission Control Technology
NOx: combustion control with overfire air + SNCR
SO2: In situ SO2 capture followed by a polishing scrubber
PM: in bed acid gas control for the condensable SO3, HCl and fluorides, followed by a fabric filter
CO: good combustion practices
VOC: good combustion practices
H2SO4: fabric filter
9. Date Permit Application Received
9/26/2007
10. Stack Height and Diameter
N/A
11. Permit Agency Contact
Melissa Byrnes
Michigan Department of Environmental Quality,
Air Quality Division,
Constitution Hall,
525 West Allegan Street
PO Box 30260
Lansing, MI, 48909 - 7760
Tel. (517) 373-7065