Oregon Clean Energy Center - Permitting Information
1. Facility Information
Oregon Clean Energy Center
2. Location
816 Lallendorf Rd.
Oregon, Ohio 43616
Lucas County
3. Distance from US/Canada Border
Approximately 40 km
4. Facility Type and Size
799 megawatt electric generating facility
5. Sources of Emissions
Two natural gas-fired combined cycle combustion turbines (2,932 mmBtu/hr heat input each) with heat recovery steam generators (300 mmBtu/hr heat input duct burner each), 99 mmBtu/hr heat input natural gas-fired auxiliary boiler, 2,250 kW emergency diesel-fired generator, 223.8 kW emergency fire water pump, 16-cell mechanical draft wet cooling tower
6. Type of Fuel
Natural gas for: turbines, duct burners and boiler; ultra-low sulfur diesel fuel for emergency generator and fire water pump
7. Type and Quantity of Emissions
Pollutant | Tons/yr |
---|---|
CO | 378.02 |
NOx | 198.96 |
PM10 | 128.17 |
PM2.5 | 123.67 |
SO2 | 36.95 |
VOC | 113.63 |
H2SO4 | 13.25 |
GHG | 2,884,330 |
Ammonia | 169.07 |
8. Emission Control Technology
Turbines/duct burners
Dry low NOx burners, SCR, catalytic oxidizer
Emergency diesel generator and fire pump
Maximum annual usage of 500 hours each
Auxiliary boiler
Low NOx burners with flue gas re-circulation, maximum 2,000 hours/yr operation
Cooling tower
Mist eliminator, total dissolved solids restriction
9. Date Permit Application Received
February 1, 2013
10. Stack Height and Diameter
Common heat recovery steam generator stack
stack height: 240 ft
inside diameter: 22 ft
Auxiliary boiler
stack height: 240 ft
inside diameter: 8 ft
Cooling Tower (12-cell)
stack height: 66 ft (each)
inside diameter: 33 ft (each)
Emergency generator
stack height: 53.5 ft
inside diameter: 0.78 ft
Emergency fire pump
stack height: 30 ft
inside diameter: 0.67 ft
11. Permit Agency Contact
Ohio Environmental Protection Agency
Lazarus Government Center
50 West Town Street, Suite 700
Columbus, OH 43215
(614) 644-3611